TSLF 36kV 1x150A

Beskrivelse

Beskrivelse

Standarder

  • Product
    HD 620 S2 2010 10M; HD 620.10K; IEC 60502-2

The cable is longitudinally and radially waterblocked and may be used for fixed installation outdoors in air, ground and water. The sheath have outer semiconducting layer.
DESCRIPTION
TSLF is a longitudinally and radially waterblocked, XLPE-insulated, copper wire screened, PE sheathed 1-core cable with circular aluminium conductor. The outer conductive layer on the insulation is crosslinked vulcanized elastomer. The cable is designed according to HD 620 10K. 

The sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.

The sheath is marked type/manufacturer/year+month/metre marking. TSLF is not flame retardant.

LIFEMARK(TM)
The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

QUALITY SYSTEM
Designed, manufactured and tested in accordance with ISO 9001.

 

Cable marking:

NEXANS TSLF XX  kV 1 x mm² MONTH YEAR, metermarking

 

Karakteristikker

Karakteristikker

Konstruksjonsegenskaper

Konstruksjonsegenskaper

Ledermateriale
Aluminium
Lederform
Rund komprimert
Materiale brukt for langsgående vanntetthet
Svellepulver
Isolasjonsskjerm
Ekstrudert
Isolasjon
Ekstrudert PEX
Lederskjerm
Ekstrudert
Skjerm
Kobbertråd
Radiell vanntetting
Ja
Skjerm/-armeringstype
Aluminiumsfolie
Ytre kappe
MDPE
Ytre ledende sjikt
Ja
Halogenfri
Ja
Leder fleksibilitet
Flertrådet, klasse 2

Dimensjonsegenskaper

Dimensjonsegenskaper

Lederdiameter
14,1 mm
Ledertverrsnitt
150 mm²
Diameter over isolert leder
31,4 mm
Nominell isolasjonstykkelse
8,0 mm
Normert skjermtverrsnitt
35 mm²
Skjermtverrsnitt Cu
21 mm²
Gj.sn. tykkelse ytre kappe
2,5 mm
Nominell ytre diameter
39,9 mm
Vekt (ca.)
1,59 kg/m
Antall ledere
1

Elektriske egenskaper

Elektriske egenskaper

Tillatt belastning i jord v/ 15 °C og 65 °C ledertemperatur - flat forlegning
315 A
Tillatt belastning i jord v/ 15 °C og 65 °C ledertemperatur - trekant forlegning
300 A
Tillatt belastning i jord v/ 15°C - flat forlegning
370 A
Tillatt belastning i jord v/ 15°C - trekant forlegning
360 A
Tillatt belastning i luft v/ 25 °C og 65 °C ledertemperatur - flat forlegning
325 A
Tillatt belastning i luft v/ 25 °C og 65 °C ledertemperatur - trekant forlegning
300 A
Tillatt belastning i luft v/ 25°C - flatforlegning
395 A
Tillatt belastning i luft v/ 25°C - trekantforlegning
370 A
Maks ledermotstand DC v/ 20 °C
0,206 Ohm/km
Maksimal AC ledermostand v/90 ºC og 50 Hz
- Ohm/km
Tillat kortslutningsstrøm leder i 1 s
14,2 kA
Nominell kapasitans leder -jord
0,18 µF / km
Reaktans flat forlegning 50 Hz
0,19 Ohm/km
Reaktans trekant 50 Hz
0,13 Ohm/km
Maks. driftsspenning
36 kV
Normert spenning i 3 fase systemer Uo/U
18 / 30 (36) kV
Skjermmotstand
- Ohm/km

Mekaniske egenskaper

Mekaniske egenskaper

Maksimal tillatt strekkstyrke
4,5 kN

Bruksegenskaper

Bruksegenskaper

Forpakning
Standardlengde
- m
Maks. Kontinuerlig ledertemperatur
90 °C
Maks. ledertemperatur v/ kortslutning
250 °C
Min. installasjonstemperatur
−20 °C
Min. bøyeradius v/gjentatt bøying eller bearbeiding
10 (xD)

Ressurser

Ressurser

Dokumentasjon

PEP pdf — 919.1 kB

Salgs- og leveringsinformasjon

Forlegning ved lave temperaturer: Kablene må behandles meget forsiktig ved temperaturer under 0 °C, spesielt må slagpåkjenninger unngås. Hvis en PEX-isolert kabels temperatur er under -10 °C ved utlegning, må man gjøre spesielle tiltak, som for eksempel oppvarming av hele trommelen, for å unngå skader på kabelen. Det er temperaturen i kabelen som er avgjørende, så en kan godt legge ut og bøye en kabel selv om lufttemperaturen er under -10 °C hvis kabelen er varmet opp på forhånd, og dens temperatur ikke synker under -10 °C ved behandlingen.

Ytelseserklæring

  • Ytelseserklæring nr. : 1000813-NOLA
  • Sertifiseringsdato : 14.03.2019
  • Verifikasjon av ytelsesdata og egenskaper : System 4
  • Deklarert ytelse : Fca

Kontakt oss

Tema som du ønsker mer informasjon om:

Påkrevde felter*

Vennligst sjekk det du har lagt inn for feil

E-postadresse må inneholde @ tegnet

Personlig databeskytter

Det er din rett å nekte behandling og analyse av dine personlige data, og deres bruk til markedsføringsformål

Tusen takk!

Takk for at du kontaktet oss, vi tar kontakt med deg snarlig.

Feil

En feil har skjedd. Vennligst prøve igjen.

Lukk