TSLF 24kV 1x50A MP

Beskrivelse

Beskrivelse

Standarder

  • Product
    HD 620.10K; IEC 60502

Single core finished marked.

The marking is carried out with a red stripe wrapped around the single conductor cables. The marking is repeated every 0.5 meters. The marking satisfies the requirement for permanent marking, which replaces the red marking tape that is put on the cable for every meter after laying.

User benefits:

Diffusion free high voltage cable

Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.

Meter marks

Screen section: Value given is the physical cross section of the copper wires in the screen.

Usage: Indoor, Underground, Outdoors

Intended for high voltage energy distribution

Fire properties:

Halogenfree
Cable marking:

NEXANS NS TSLF  kV 1 x mm²/mm² MONTH YEAR, metermarks

Lifemark

Karakteristikker

Karakteristikker

Konstruksjonsegenskaper

Konstruksjonsegenskaper

Ledermateriale
Aluminium
Lederform
Rund komprimert
Materiale brukt for langsgående vanntetthet
Svellepulver
Isolasjonsskjerm
Ekstrudert
Isolasjon
Ekstrudert PEX
Lederskjerm
Ekstrudert
Skjerm
Kobbertråd
Radiell vanntetting
Ja
Skjerm/-armeringstype
Aluminiumsfolie
Ytre kappe
MDPE
Ytre ledende sjikt
Ja
Halogenfri
Ja
Leder fleksibilitet
Flertrådet, klasse 2

Dimensjonsegenskaper

Dimensjonsegenskaper

Lederdiameter
8,0 mm
Ledertverrsnitt
50 mm²
Diameter over isolert leder
19,3 mm
Nominell isolasjonstykkelse
5,5 mm
Normert skjermtverrsnitt
16 mm²
Skjermtverrsnitt Cu
10 mm²
Gj.sn. tykkelse ytre kappe
2,1 mm
Nominell ytre diameter
27,0 mm
Vekt (ca.)
0,684 kg/m
Antall ledere
1

Elektriske egenskaper

Elektriske egenskaper

Tillatt belastning i jord v/ 15 °C og 65 °C ledertemperatur - flat forlegning
170 A
Tillatt belastning i jord v/ 15 °C og 65 °C ledertemperatur - trekant forlegning
155 A
Tillatt belastning i jord v/ 15°C - flat forlegning
200 A
Tillatt belastning i jord v/ 15°C - trekant forlegning
185 A
Tillatt belastning i luft v/ 25 °C og 65 °C ledertemperatur - flat forlegning
165 A
Tillatt belastning i luft v/ 25 °C og 65 °C ledertemperatur - trekant forlegning
160 A
Tillatt belastning i luft v/ 25°C - flatforlegning
205 A
Tillatt belastning i luft v/ 25°C - trekantforlegning
195 A
Maks ledermotstand DC v/ 20 °C
0,641 Ohm/km
Tillat kortslutningsstrøm leder i 1 s
4,7 kA
Nominell kapasitans leder -jord
0,16 µF / km
Nullreaktans (50 Hz)
- Ohm/km
Reaktans flat forlegning 50 Hz
0,22 Ohm/km
Reaktans trekant 50 Hz
0,14 Ohm/km
Maks. driftsspenning
24 kV
Normert spenning i 3 fase systemer Uo/U
12 / 20 (24) kV

Mekaniske egenskaper

Mekaniske egenskaper

Maksimal tillatt strekkstyrke
1,5 kN
Min. bøyediameter v/ gjentatt bøying
540 mm

Bruksegenskaper

Bruksegenskaper

Forpakning
NX14
Standardlengde
1000 m
Maks. Kontinuerlig ledertemperatur
90 °C
Maks. ledertemperatur v/ kortslutning
250 °C
Min. installasjonstemperatur
−20 °C
Min. bøyeradius v/gjentatt bøying eller bearbeiding
10 (xD)

Ressurser

Ressurser

Dokumentasjon

PEP pdf — 919.1 kB

Salgs- og leveringsinformasjon

Kablene må behandles meget forsiktig ved temperaturer under 0 °C, spesielt må slagpåkjenninger unngås. Hvis en PEX-isolert kabels temperatur er under -10 °C ved utlegning, må man gjøre spesielle tiltak, som for eksempel oppvarming av hele trommelen, for å unngå skader på kabelen. Det er temperaturen i kabelen som er avgjørende, så en kan godt legge ut og bøye en kabel selv om lufttemperaturen er under -10 °C hvis kabelen er varmet opp på forhånd, og dens temperatur ikke synker under -10 °C ved behandlingen.

Kontakt oss

Tema som du ønsker mer informasjon om:

Påkrevde felter*

Vennligst sjekk det du har lagt inn for feil

E-postadresse må inneholde @ tegnet

Personlig databeskytter

Det er din rett å nekte behandling og analyse av dine personlige data, og deres bruk til markedsføringsformål

Tusen takk!

Takk for at du kontaktet oss, vi tar kontakt med deg snarlig.

Feil

En feil har skjedd. Vennligst prøve igjen.

Lukk