PFSP 1kV 4x50A/16

Description

Description

Standards

  • Product
    HD 603.3J
  • Test
    EN 50265; IEC 60332-1

Recommended for use in all room types, and outdoors in-ground without extra protection. Suitable for low voltage systems i.e. 230V, 400V and 690V.

The copper screen is dimensioned to fulfill the requirements for earth conductor (PE) or  combined earth- and neutral conductor (PEN). The screen is made of copper wires with a counter helix to ensure contact between the individual wires. The cable meets the fire classification according to CPR class E.

 

Min. installation temperature without extra precautions: 0°C

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Sector-shaped stranded (SM)
Conductor material
Aluminum
Core identification
Colours
Insulation
PVC
Outer sheath
PVC
Conductor flexibility
Class 2
Lead free
Yes
Sheath colour
Grey
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Screen section
16 mm²
Conductor diameter
- mm
Nominal outer diameter
31.0 mm
Number of cores
4
Neutral conductor section (when smaller)
- mm²
Number of strands
7
Sector-shaped heigth
6.9 mm
Conductor cross-section
50 mm²
Approximate weight
124.0 kg/100m
Sector-shaped width
10.6 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Bending factor when installed
- (xD)
Installation type
Outdoor - Direct burial
Length
500 m
Packaging
Drum
Max. conductor temperature in service
70 °C

Resources

Resources

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 110.0 86.0 133.0 104.0 168.0 125.0 140.0 109.0 156.0 117.0 180.0 135.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 99.0 78.0 118.0 92.0 144.0 110.0 116.0 91.0 130.0 99.0 153.0 117.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Selling & delivery Information

The cable is marked with LIFEMARK™

Declaration of Performance

  • Declaration of Performance n� : 1000126-SEGR
  • Certification Date : 2/9/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close