PFSP 1kV 4x240A/70
PFSP 1kV 4x240A/70
Installation cable with aluminium conductor
Read more- Nexans ref. : 10021748
- Country ref. : 1067099
- EAN : 7330000055759
Description
Description
Standards
-
ProductHD 603.3J
-
TestEN 50265; IEC 60332-1
Recommended for use in all room types, and outdoors in-ground without extra protection. Suitable for low voltage systems i.e. 230V, 400V and 690V.
The copper screen is dimensioned to fulfill the requirements for earth conductor (PE) or combined earth- and neutral conductor (PEN). The screen is made of copper wires with a counter helix to ensure contact between the individual wires. The cable meets the fire classification according to CPR class E.
Min. installation temperature without extra precautions: 0°C
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor shape
Sector-shaped stranded (SM)
Conductor material
Aluminum
Core identification
Colours
Insulation
PVC
Outer sheath
PVC
Conductor flexibility
Class 2
Lead free
Yes
Sheath colour
Grey
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Screen section
70 mm²
Conductor diameter
- mm
Nominal outer diameter
59.0 mm
Number of cores
4
Neutral conductor section (when smaller)
- mm²
Number of strands
37
Sector-shaped heigth
23 mm
Conductor cross-section
240 mm²
Approximate weight
490.0 kg/100m
Sector-shaped width
16.3 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Usage characteristics
Usage characteristics
Bending factor when installed
- (xD)
Installation type
Outdoor - Direct burial
Length
400 m
Packaging
R22
Max. conductor temperature in service
70 °C
Resources
Resources
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
240.0 | 291.0 | 229.0 | 344.0 | 269.0 | 461.0 | 352.0 | 336.0 | 262.0 | 382.0 | 298.0 | 514.0 | 380.0 |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single-core or Multi-core cable in ducts in the ground |
D2 Single-core or Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
240.0 | 261.0 | 207.0 | 297.0 | 232.0 | 403.0 | 305.0 | 280.0 | 218.0 | 320.0 | 250.0 | 430.0 | 330.0 |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single-core or Multi-core cable in ducts in the ground |
D2 Single-core or Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Selling & delivery Information
The cable is marked with LIFEMARK™
Declaration of Performance
- Declaration of Performance n� : 1000126-SEGR
- Certification Date : 2/9/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0366
- Declared performance : Eca