PFSP 1kV 2x16/16

Description

Description

Standards

  • Product
    HD 603.3J
  • Test
    EN 50265; IEC 60332-1

Recommended for indoor and outdoor use in all areas, and can be installed directly in the ground without extra protection. PFSP 1kV is suitable for all low voltage systems i.e 230V, 400V and 690V.

The copper screen is dimensioned to fulfill the requirements for earth conductor (PE) or combined earth- and neutral conductor (PEN). The copper screen is made of copper wires with a counter helix to ensure contact between the wires. 

If the cable is cut outdoor, any end(s) must be sealed if not connected/terminated. This to prevent water intrusion, and possible corrosion in the future.

Min. installation temperature without extra precautions: 0 °C

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor shape
Circular
Material of bedding
Lapped inner covering
With Green/Yellow core
No
With smaller neutral conductor
No
Sheath colour
Grey
Type of conductor
Circular, stranded
Conductor material
Bare annealed copper stranded
Core identification
Colours
Insulation
PVC
Lead free
Yes
Screen
Copper wires / 6mm²
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Screen section
16 mm²
Conductor diameter
4.8 mm
Nominal outer diameter
20.0 mm
Number of cores
2
Neutral conductor section (when smaller)
- mm²
Sector-shaped heigth
- mm
Conductor cross-section
16 mm²
Approximate weight
70.0 kg/100m
Sector-shaped width
- mm
Approximate weight
700 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Bending factor when laying
8 (xD)
Maximum operating temperature
70 °C
RoHS compliant
Yes

Resources

Resources

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 57.0 44.0 69.0 54.0 85.0 66.0 78.0 61.0 83.0 63.0 94.0 73.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 52.0 41.0 62.0 48.0 76.0 59.0 64.0 50.0 70.0 53.0 80.0 61.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Selling & delivery Information

The cable is marked with LIFEMARK™.

Declaration of Performance

  • Declaration of Performance n� : 1000321-SEGR
  • Certification Date : 7/26/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.