PR 3x4/4 mm²

Description

Description

Standards

  • International
    IEC 60332-1-2
  • National
    NEK 535

Installation cable for surface mount/visible installations. Can be used indoor and outdoor, but not suitable for being buried in the ground.

Minimum bending diameter, one-time 90 degree bend: 2xD
Minimum bending diameter, sharper bends: 4xD
(D = Outer diameter of cable)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Solid class 1
Conductor material
Bare annealed copper stranded
Conductor shape
Round, massive
Insulation
PVC
Lead free
Yes
Material of filler / inner sheath
Yes
Outer sheath
PVC
Screen
Longitudinal aluminium tape + copper wire
Sheath colour
White
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
272 kg/km
Approximate weight
27.2 kg/100m
Conductor cross-section
4 mm²
Conductor diameter
2.3 mm
Height
- mm
Nominal outer diameter
11.5 mm
Number of cores
3
Width
- m

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V

Usage characteristics

Usage characteristics

Ambient installation temperature
10 °C
Field of application
Indoor, Outdoor
Max. conductor temperature in service
70 °C
Packaging
Coil
RoHS compliant
Yes

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000014-NOLA
  • Certification Date : 1/9/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0402
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close