PVXP 250V 2x1/1 mm Utgått.

Description

Description

Standards

  • Test
    EN 50265; IEC 60332-1-2
  • National
    NEK 535

Recommended as signal cable for fire alarm installations indoors and outdoors. Not suitable for installation in the ground. Parallel conductors.

NB! Replaced by IFLI Easy-R 250V, click here: Nexans - IFLI EASY-R 250 V ALSECURE brannalarmkabel

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Sheath colour
White
Type of conductor
Circular, solid
Conductor material
Bare annealed copper stranded
Insulation
PVC
Lead free
Yes
Outer sheath
PVC
Conductor flexibility
Solid class 1
Conductor shape
Round, massive
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Conductor diameter
1.0 mm
Nominal outer diameter
6.6 mm
Number of cores
2
Number of strands
1
Screen section
0.8 mm²
Conductor cross-section
0.8 mm²
Approximate weight
7.0 kg/100m
Approximate weight
70 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
250 V

Usage characteristics

Usage characteristics

Length
500 m
Packaging
Drum
Max. conductor temperature in service
70 °C
Flame retardant
IEC 60332-1-2
RoHS compliant
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close