250V RFOU(I) [S101] (Multi triads, 0.75 1.0)
250V RFOU(I) [S101] (Multi triads, 0.75 1.0)
Application
- Instrument circuit up to 250V, instrument safe systems.
- Fixed installation for instrument, communication, control and alarm systems in both explosion risk and safe areas, general purposes.
- Maximum operating conductor temperature 90°C
Description
Description
Standards
-
ProductUL 1581
-
InstallationIEC 60092-360; IEC 60092-376
-
TestCSA C22.2 N° 03-01; IEC 60332-3 Cat.A; IEC 60684-2; IEC 60754-1; IEC 60754-2; IEC 61034
-
NationalNEK 606
Construction Details
- Conductor : Circular tinned stranded copper as per IEC 60228, Class 2
- Insulation : Halogen Free Ethylene Propylene Rubber
- Triple twisting : Three insulated cores twisted together with suitable lay length
- Individual screening : Wrapped by copper or aluminium backed polyester tape with tinned copper drain wire
- Cabling (with filler)
- Collective screening (option) : Wrapped by copper or aluminium backed polyester tape with tinned copper drain wire
- Inner covering : Halogen free compound
- Armour : Tinned copper wire braid as per IEC 60092-376
- RFCU (option) : Galvanized steel wire braid as per IEC 60092-376
- Outer sheath : Halogen free thermosetting compound as per IEC 60092-360, SHF2 or SHF2 Oil & Mud
Standard Applied
- Design guideline : IEC 60092-376 & NEK 606-2016
- Material
Insulation : EPR, IEC 60092-360
Sheath : SHF2, IEC 60092-360
- Flame retardant : IEC 60332-3-22, Cat.A
- Halogen free properties : IEC 60754-1,2 & IEC 60684-2
- Low smoke properties : IEC 61034-1,2
- Sunlight resistance : UL 1581
- Cold properties (option) : CSA C22.2 No.03 (Bending : -40C, Impact : -35C)
- Oil/Mud resistance (option) : NEK 606-2016 (Category a, b, c, d)
Identification of color
- Insulation
- 1Triple : Black, Light Blue, Brown
- 2Triple and above : Numbering on Black, Light Blue & Brown insulation core
Note) Any other colors purchaser required
- Outer sheath : Grey (or Light blue for I.S. cable)
Note) Any other colors purchaser required
Type approval
- ABS, BV, DNV, LR
Marking
NEXANS KUKDONG S101 RFOU(I) 250V 7TRx1.5 SQMM IEC 60332-3 A year length
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania