TXRA 24kV 3x50Cu GS48 R3.2 Zn

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-2; Nexans specification

Armored PEX insulated submarine cables for utilities.

 

Construction:
 

Conductor:
Round multiple wire, compressed copper conductor

Conductor screen:
Extruded layer of semi-conductive cross-linked polyethylene.

Insulation:
Extruded insulation of cross-linked polyethylene.

Insulation screen:

Extruded insulation of cross-linked polyethylene.

Twisting and bonding:
Three insulated conductors are twisted together and bonded with semiconducting bands.
Fillers are installed in the winding rooms.
If desired, fiber cables can also be inserted into the winding rooms.

Armouring:
A layer of galvanized steel wires, 3.2mm.
Zinc wires can be inserted into the reinforcement if desired.

Outer corrosion protection:
Two layers of polypropylene yarn with bitumen.

 

The dimensions and weights given are based on IEC 60502 and 3.2 mm reinforcement wire. In other cases, the values ​​given will vary.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Conductor shape
Circular compacted
Material of the inner semi-conductor
Extruded
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
Extruded
Armour type
Galvanised round steel wires
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor diameter
8.2 mm
Diameter over insulation
24.5 mm
Nominal insulation thickness
5.5 mm
Diameter of steel wires
3.2 mm
Nominal outer diameter
71.0 mm
Approximate weight
6100 kg/km
Approximate weight in seawater
3400 kg/km
Conductor cross-section
50 mm²
Number of cores
3
Number of optical fibres
48

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
Maximum operating voltage
24 kV
Permissible current rating when buried
215 A
Permissible current rating in open air
225 A
Permissible current rating submerged in water, 15°C ambient temperature
230 A
Nominal phase capacitance
0.188 µF / km
Nominal inductance
0.425 mH/km
Permissible short circuit current conductor 1s
7.6 kA
Permissible short circuit current screen 1s
2.8 kA
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Reactance at 50 Hz
0.133 Ohm/km
Zero sequence reactance at 50HZ
- Ohm/km
Zero sequence resistance at 20°C
- Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
26.9 kN

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)
Minimum installation temperature
-10 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close