TXVA 24kV 3x95Cu GS48 R5.0/5.0 Zn

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-2; Nexans specification

User benefits:

 

Construction:
 

Conductor:
Round multiple wire, compressed copper conductor

Conductor screen:
Extruded layer of semi-conductive cross-linked polyethylene.

Insulation:
Extruded insulation of cross-linked polyethylene.

Insulation screen:

Extruded insulation of cross-linked polyethylene.

Twisting and bonding:
Three insulated conductors are twisted together and bonded with semiconducting bands.
Fillers are installed in the winding rooms.
If desired, fiber cables can also be inserted into the winding rooms.

Armouring:
2 layers of galvanized steel wires.
Zinc wires can be inserted into the reinforcement if desired.

Outer corrosion protection:
Two layers of polypropylene yarn with bitumen.

 

The dimensions and weights given are based on IEC 60502. In other cases, the values ​​given will vary.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Galvanised round steel wires
Conductor flexibility
Stranded class 2
Conductor material
Annealed copper
Conductor shape
Circular compacted
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
Extruded
Material of the inner semi-conductor
Extruded

Dimensional characteristics

Dimensional characteristics

Nominal outer diameter
86.7 mm
Approximate weight
15500 kg/km
Approximate weight in seawater
9800 kg/km
Conductor cross-section
95 mm²
Conductor diameter
11.5 mm
Diameter of steel wires
5 mm
Diameter over insulation
25.8 mm
Nominal insulation thickness
5.5 mm
Number of cores
3
Number of optical fibres
48

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
330 A
Permissible current rating when buried
315 A
Permissible current rating submerged in water, 15°C ambient temperature
335 A
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Maximum operating voltage
24 kV
Nominal inductance
0.382 mH/km
Nominal phase capacitance
0.233 µF / km
Permissible short circuit current conductor 1s
14.2 kA
Permissible short circuit current screen 1s
3.2 kA
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Reactance at 50 Hz
0.12 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
66.9 kN

Usage characteristics

Usage characteristics

Bending factor when laying
20 (xD)
Max. conductor temperature in service
90 °C
Maximum deployment ocean depth
1200 m
Minimum installation temperature
-10 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close