RXQ/TXXI 1kV 1x 95mm²Cu
Nexans ref. 10255012 - Country ref. 1017540
- Packaging: Drum (500m)
- Conductor diameter: 12.3 mm
- Diameter over insulation: 14.5 mm
- Nominal outer diameter: 17.5 mm
- Approximate weight: 965 kg/km
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
RXQ/TXXI 1kV 1x150mm²Cu
Nexans ref. 10255013 - Country ref. 1017541
- Packaging: Drum (500m)
- Conductor diameter: 16.7 mm
- Diameter over insulation: 19.5 mm
- Nominal outer diameter: 22.7 mm
- Approximate weight: 1540 kg/km
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
RXQ/TXXI 1kV 1x185 mm²Cu
Nexans ref. 10580933
- Packaging: Drum (500m)
- Conductor diameter: 18.7 mm
- Diameter over insulation: 25.1 mm
- Nominal outer diameter: 20.9 mm
- Approximate weight: 1770 kg/km
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
RXQ/TXXI 1kV 1x240mm²Cu
Nexans ref. 10255014 - Country ref. 1017542
- Packaging: Drum (500m)
- Conductor diameter: 21.3 mm
- Diameter over insulation: 24.7 mm
- Nominal outer diameter: 28.1 mm
- Approximate weight: 2410 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0801 Ohm/km
RXQ/TXXI 1kV 1x300mm²Cu
Nexans ref. 10255015 - Country ref. 1017543
- Packaging: Drum (500m)
- Conductor diameter: 24.0 mm
- Diameter over insulation: 27.7 mm
- Nominal outer diameter: 31.2 mm
- Approximate weight: 3100 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0641 Ohm/km
RXQ/TXXI 1kV 1x400mm²Cu
Nexans ref. 10255016 - Country ref. 1017544
- Packaging: Drum (500m)
- Conductor diameter: 27.4 mm
- Diameter over insulation: 31.4 mm
- Nominal outer diameter: 35.2 mm
- Approximate weight: 3900 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0486 Ohm/km
Description
Description
Standards
-
ProductIEC 60228
-
TestEN 50267-2-1; EN 50267-2-2; EN 50268-2; IEC 60754-1; IEC 60754-2; IEC 61034
-
NationalNEK 536
Description
RXQ/TXXI (S1XZ1-K) is a halogen free, XLPE-insulted and HFFR sheathed cable with circular and multi stranded copper conductor. The cable is designed according to SS 424 14 18. The conductors have resistance according to IEC 60228 class 5. The sheath is marked "NEXANS GS AREA mm2 1kV Ds2d2a2 year+month". RXQ/TXXI meets the requirements for flame class Dcas2d2a2 according to CPR.
Lifemark(TM) recycling marking
The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.
Quality system
Designed, manufactured and tested in accordance with ISO 9001.
Environmental management system
The activities at our plant in Grimsås are certified according to ISO 14001.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics