TFXP 1kV 4G95A
TFXP 1kV 4G95A
- Nexans ref. : 10022129
- Country ref. : 1017592
- EAN : 7330000055834
Description
Description
Standards
-
ProductHD 603.5M
-
TestIEC 60332-1
User benefits:
TFXP has XLPE-insulated aluminium conductors.
The cable is specially devoloped for low temperature conditions.
Installation:
- Underground
- Outdoor
Usage
- Energy distribution
Marking
NEXANS GS TFXP n x mm2 1kV YEAR MONTH
Conductor marking/colour code
Black-Brown-Grey-Green/Yellow
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Sector-shaped stranded (SM)
Insulation
XLPE (chemical)
With Green/Yellow core
Yes
Material of filler / inner sheath
PE
Outer sheath
PVC
Sheath colour
Green
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
95 mm²
Conductor diameter
- mm
Sector-shaped heigth
12.4 mm
Sector-shaped width
17.4 mm
Number of cores
4
Nominal outer diameter
38.0 mm
Approximate weight
1.6 kg/m
Diameter over inner sheath
2 mm
Nominal insulation thickness
1.1 mm
Nominal outer sheath thickness
1.5 mm
Electrical characteristics
Electrical characteristics
Permissible current rating in open air
245 A
Permissible current rating when buried
260 A
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Inductive reactance at 50Hz
0.075 Ohm/km
Nominal inductance
0.23 mH/km
Zero sequence reactance at 50HZ
0.31 Ohm/km
Zero sequence resistance at 20°C
1.28 Ohm/km
Capacity of phase cores approx.
0.12 µF / km
Permissible short circuit current conductor 1s
8.6 kA
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
11.4 kN
Minimum repeated bending diameter
456 mm
Usage characteristics
Usage characteristics
Packaging
NX16
Length
600 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-10 °C
Bending factor when laying
6 (xD)
Flame retardant
IEC 60332-1