TXXI-O-RL 1kV 5G25A

Description

Description

Standards

  • Product
    HD 603.5J
  • Test
    IEC 60332-1-2

Power distribution cable, designated for road lights, entry point installation or other general outdoor use (UV-resistant).

The cable is fire-retardant and halogen free, each phase having insulation and an outer sheath.

Can be placed directly in soil.

When laying at a lower temperatures than 0 degrees Celsius, care must be taken to avoid damage to the outer sheath. It is especially important that the cable is not exposed to impact at temperatures below 0  °C.

When laying at lower temperatures than -10 degrees Celsius, the cable should be preheated before laying as well.

If the cable is cut and not installed immediately, each phase must be sealed, to prevent water intrusion.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Type of conductor
Circular compacted stranded
Insulation
XLPE (chemical)
With Green/Yellow core
Yes
Halogen free
Yes
Outer sheath
Halogen free, fire retardant
Conductor flexibility
Stranded class 2
Conductor shape
Round, stranded

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
25 mm²
Conductor diameter
5.8 mm
Number of cores
5
Diameter over insulation
7.6 mm
Nominal outer diameter
31.0 mm
Tube diameter
8 mm
Inner diameter
4.4 mm
Approximate weight
0.8 kg/m

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
110 A
Permissible current rating when buried
135 A
Max. DC resistance of the conductor at 20°C
1.2 Ohm/km
Inductive reactance at 50Hz
0.099 Ohm/km
Nominal inductance
0.31 mH/km
Capacity of phase cores approx.
0.09 µF / km
Zero sequence reactance at 50HZ
0.41 Ohm/km
Zero sequence resistance at 20°C
4.8 Ohm/km
Permissible short circuit current conductor 1s
2.4 kA
Maximum operating voltage
1000 V
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
3.75 kN
Minimum repeated bending diameter
372 mm

Usage characteristics

Usage characteristics

Packaging
NX14
Length
1000 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-15 °C
Bending factor when laying
6 (xD)
Flame retardant
IEC 60332-1-2
RoHS compliant
Yes

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000974-NOLA
  • Certification Date : 1/26/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close