TSLF(HD) 24kV 1x150A

Description

Description

Standards

  • Product
    HD 620.10K
  • Test
    IEC 60840

User benefits:

Diffusion free high voltage cable

Avoids threfore growth of watertrees in the XLPE insulation which increases the lifetime.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc. 

Meter marks

Screen section: Value given is the physical cross section of the copper wires in the screen.

 

Usage: Indoor, Underground, Outdoors

 

Intended for high voltage energy distribution

Fire properties:

Halogenfree
 

Cable marking:

NEXANS NS TSLF  kV 1 x mm²/mm² MONTH YEAR, metermarks

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
HDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
-

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
150 mm²
Conductor diameter
14.1 mm
Diameter over insulation
25.4 mm
Average insulation thickness
5.5 mm
Earth conductor cross section
25 mm²
Screen section
15 mm²
Average sheath thickness
2.3 mm
Nominal outer diameter
33.7 mm
Approximate weight
1.19 kg/m
Number of cores
-

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - flat formation
370 A
Perm. current rating buried 15°C - trefoil formation
355 A
Perm. current rating in air 25°C - flat formation
395 A
Perm. current rating in air 25°C - trefoil formation
370 A
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Permissible short circuit current conductor 1s
13.5 kA
Nominal phase capacitance
0.23 µF / km
Inductive reactance at 50Hz
- Ohm/km
Nominal inductance
- mH/km
Phase reactance 50 Hz - flat formation
0.19 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.12 Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
4.5 kN
Minimum repeated bending diameter
674 mm

Usage characteristics

Usage characteristics

Packaging
NX16
Length
1000 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
10 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close