TSLF(HD) 24kV 1x630A

Description

Description

Standards

  • Product
    HD 620.10K
  • Test
    IEC 60840

User benefits:

Diffusion free high voltage cable

Avoids threfore growth of watertrees in the XLPE insulation which increases the lifetime.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc. 

Meter marks

Screen section: Value given is the physical cross section of the copper wires in the screen.

Usage: Indoor, Underground, Outdoors

Intended for high voltage energy distribution

Fire properties:

Halogenfree
 

Cable marking:

NEXANS NS TSLF  kV 1 x mm²/mm² MONTH YEAR, metermarks

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
HDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
-

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
630 mm²
Conductor diameter
30.1 mm
Diameter over insulation
41.7 mm
Average insulation thickness
5.5 mm
Earth conductor cross section
50 mm²
Screen section
31 mm²
Average sheath thickness
2.8 mm
Nominal outer diameter
50.1 mm
Approximate weight
3.17 kg/m
Number of cores
-

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - flat formation
715 A
Perm. current rating buried 15°C - trefoil formation
745 A
Perm. current rating in air 25°C - flat formation
840 A
Perm. current rating in air 25°C - trefoil formation
880 A
Max. DC resistance of the conductor at 20°C
0.0469 Ohm/km
Permissible short circuit current conductor 1s
56.7 kA
Nominal phase capacitance
0.43 µF / km
Inductive reactance at 50Hz
- Ohm/km
Nominal inductance
- mH/km
Phase reactance 50 Hz - flat formation
0.15 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.09 Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
18.9 kN
Minimum repeated bending diameter
1002 mm

Usage characteristics

Usage characteristics

Packaging
NX20
Length
500 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
10 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close