TSLF 24kV 3x1x400A

Description

Description

Standards

  • Product
    HD 620.10K

User benefits:

Diffusion free high voltage cable.

Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.

Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.

Screen section: Value given is the physical cross section of the copper wires in the screen of one core.

Usage:

Indoor

Underground

Outdoors

Intended for high voltage energy distribution

Fire propertirs:

Halogen free

Cable marking:

NEXANS NS TSLF 12 kV 1 x mm²/mm² MONTH YEAR

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
MDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
400 mm²
Conductor diameter
23.6 mm
Diameter over insulation
35.1 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
35 mm²
Screen section
21 mm²
Average sheath thickness
2.6 mm
Nominal outer diameter
95.5 mm
Approximate weight
6.723 kg/m
Number of cores
3

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - flat formation
590 A
Perm. current rating buried 15°C - trefoil formation
615 A
Perm. current rating buried, 65°C conductor temperature, 15°C ambient – flat
502 A
Perm. current rating in air 25°C - flat formation
680 A
Perm. current rating in air 25°C - trefoil formation
680 A
Permissible current rating buried, 65°C conductor temperature, 15°C ambient – trefoil
510 A
Permissible current rating in air, 65°C conductor temperature, 25°C ambient – flat
555 A
Permissible current rating in air, 65°C conductor temperature, 25°C ambient – trefoil
555 A
Max. DC resistance of the conductor at 20°C
0.0778 Ohm/km
Permissible short circuit current conductor 1s
37.8 kA
Nominal phase capacitance
0.37 µF / km
Phase reactance 50 Hz - trefoil formation
0.1 Ohm/km
Maximum operating voltage
24 kV
AC resistance at 110°C, 60Hz
- Ohm/kft
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
36 kN
Minimum repeated bending diameter
478 mm

Usage characteristics

Usage characteristics

Packaging
NX26
Length
500 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)

Resources

Resources

Documentation

PEP pdf — 919.4 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close