TSLF 24kV 3x1x630A
TSLF 24kV 3x1x630A
Metal screened cable with laminated aluminium sheet and outer semiconducting layer. Tree twisted cores.
Read more- Nexans ref. : 10558139
- Country ref. : 1067137
- EAN : 7045210125306
Description
Description
Standards
-
ProductHD 620.10K
User benefits:
Diffusion free high voltage cable.
Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.
Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.
Screen section: Value given is the physical cross section of the copper wires in the screen of one core.
Usage:
Indoor
Underground
Outdoors
Intended for high voltage energy distribution
Fire propertirs:
Halogen free
Cable marking:
NEXANS NS TSLF 12 kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
MDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
630 mm²
Conductor diameter
30.1 mm
Diameter over insulation
41.7 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
50 mm²
Screen section
31 mm²
Average sheath thickness
2.8 mm
Nominal outer diameter
110.0 mm
Approximate weight
9.558 kg/m
Number of cores
3
Electrical characteristics
Electrical characteristics
Perm. current rating buried 15°C - flat formation
715 A
Perm. current rating buried 15°C - trefoil formation
780 A
Perm. current rating buried, 65°C conductor temperature, 15°C ambient – flat
608 A
Perm. current rating in air 25°C - flat formation
840 A
Perm. current rating in air 25°C - trefoil formation
880 A
Permissible current rating buried, 65°C conductor temperature, 15°C ambient – trefoil
635 A
Permissible current rating in air, 65°C conductor temperature, 25°C ambient – flat
685 A
Permissible current rating in air, 65°C conductor temperature, 25°C ambient – trefoil
720 A
Max. DC resistance of the conductor at 20°C
0.0469 Ohm/km
Permissible short circuit current conductor 1s
59.5 kA
Nominal phase capacitance
0.43 µF / km
Phase reactance 50 Hz - trefoil formation
0.09 Ohm/km
Maximum operating voltage
24 kV
AC resistance at 110°C, 60Hz
- Ohm/kft
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
56.7 kN
Minimum repeated bending diameter
550 mm
Usage characteristics
Usage characteristics
Packaging
NX26
Length
350 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)