TSLF-J 24 - 36kV single core with copper wire
TSLF-J 24 - 36kV single core with copper wire
Metal screened cable with laminated aluminium and outer semiconducting layer. One ground wire is attached to the oversheet.
Read moreTSLF-J 24kV 1x50A KGF50
Nexans ref. 10581199 - Country ref. 1007990
- Packaging: Drum (1000m)
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 27.0 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 200 A
- Perm. current rating buried 15°C - trefoil formation: 180 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 1.5 kN
TSLF-J 24kV 1x95A KGF25
Nexans ref. 10224444 - Country ref. 1021213
- Packaging: Drum (1000m)
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 30.6 mm
- Ground conductor cross-section: 25 mm²
- Perm. current rating buried 15°C - flat formation: 290 A
- Perm. current rating buried 15°C - trefoil formation: 265 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 2.85 kN
TSLF-J 24kV 1x95A KGF50
Nexans ref. 10224450 - Country ref. 1021219
- Packaging: Drum (1000m)
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 30.6 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 290 A
- Perm. current rating buried 15°C - trefoil formation: 265 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 2.85 kN
TSLF-J 36kV 1x150A KGF50
Nexans ref. 10266325
- Packaging: Drum (1000m)
- Conductor cross-section: 150 mm²
- Nominal outer diameter: 39.9 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 350 A
- Perm. current rating buried 15°C - trefoil formation: 340 A
- Maximum operating voltage: 36 kV
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Maximum Pulling Tension: 4.5 kN
TSLF-J 24kV 1x240A KGF25
Nexans ref. 10224446 - Country ref. 1021215
- Packaging: Drum (1000m)
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 38.1 mm
- Ground conductor cross-section: 25 mm²
- Perm. current rating buried 15°C - flat formation: 585 A
- Perm. current rating buried 15°C - trefoil formation: 445 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 7.2 kN
TSLF-J 24kV 1x240A KGF50
Nexans ref. 10224452 - Country ref. 1021229
- Packaging: Drum (1000m)
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 38.1 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 465 A
- Perm. current rating buried 15°C - trefoil formation: 445 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 7.2 kN
TSLF-J 36kV 1x240A KGF50
Nexans ref. 10266327
- Packaging: Drum (1000m)
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 44.2 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 450 A
- Perm. current rating buried 15°C - trefoil formation: 450 A
- Maximum operating voltage: 36 kV
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Maximum Pulling Tension: 7.2 kN
TSLF-J 24kV 1x400A KGF25
Nexans ref. 10224447 - Country ref. 1021216
- Packaging: Drum (1000m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 44.3 mm
- Ground conductor cross-section: 25 mm²
- Perm. current rating buried 15°C - flat formation: 585 A
- Perm. current rating buried 15°C - trefoil formation: 575 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 12 kN
TSLF-J 24kV 1x400A KGF50
Nexans ref. 10224453 - Country ref. 1021236
- Packaging: Drum (1000m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 44.3 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 585 A
- Perm. current rating buried 15°C - trefoil formation: 575 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 12 kN
TSLF-J 36kV 1x400A KGF50
Nexans ref. 10266329
- Packaging: Drum (1000m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 50.4 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 565 A
- Perm. current rating buried 15°C - trefoil formation: 580 A
- Maximum operating voltage: 36 kV
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Maximum Pulling Tension: 12 kN
TSLF-J 24kV 1x630A KGF25
Nexans ref. 10224448 - Country ref. 1021217
- Packaging: Drum (1000m)
- Conductor cross-section: 630 mm²
- Nominal outer diameter: 50.1 mm
- Ground conductor cross-section: 25 mm²
- Perm. current rating buried 15°C - flat formation: 710 A
- Perm. current rating buried 15°C - trefoil formation: 735 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 18.9 kN
TSLF-J 24kV 1x630A KGF50
Nexans ref. 10224454 - Country ref. 1021237
- Packaging: Drum (1000m)
- Conductor cross-section: 630 mm²
- Nominal outer diameter: 50.1 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 710 A
- Perm. current rating buried 15°C - trefoil formation: 735 A
- Maximum operating voltage: 24 kV
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Maximum Pulling Tension: 18.9 kN
TSLF-J 36kV 1x630A KGF50
Nexans ref. 10266331
- Packaging: Drum (1000m)
- Conductor cross-section: 630 mm²
- Nominal outer diameter: 57.9 mm
- Ground conductor cross-section: 50 mm²
- Perm. current rating buried 15°C - flat formation: 675 A
- Perm. current rating buried 15°C - trefoil formation: 740 A
- Maximum operating voltage: 36 kV
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Maximum Pulling Tension: 18.9 kN
Description
Description
Standards
-
ProductHD 620.10K
User benefits:
Diffusion free high voltage cable. Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime.
The semiconducting layer makes it easy to test the outer sheats integrity while on drum, before backfilling, in plastic tubes etc.
Screen section: Value given is the physical cross section of the copper wires in one core.
The cable has one groud wire attached to the oversheet.
Usage:
Indoor
Underground
Outdoors
Intended for high voltage energy distribution
Fire properties:
Halogen free
Cable marking:
NEXANS NS TSLF xx kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania