TSLF-O 24kV 3x1x630A
TSLF-O 24kV 3x1x630A
TSLF-O 24kV 3x1x630A 14 mm rør
Read more- Nexans ref. : 10558141
- Country ref. : 1087898
Description
Description
Standards
-
ProductHD 620.10K
User benefits:
Diffusion free high voltage cable. Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime.
The semiconducting layer makes it easy to test the outer sheats integrity while on drum, before backfilling, in plastic tubes etc.
The cable has three tubes for future installation of optical cables.
Usage:
Indoor
Underground
Outdoors
Intended for high voltage energy distribution
Fire properties:
Halogen free
Cable marking:
NEXANS NS TSLF XX kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
MDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
630 mm²
Conductor diameter
31.1 mm
Diameter over insulation
41.7 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
50 mm²
Screen section
31 mm²
Average sheath thickness
2.8 mm
Nominal outer diameter
110.0 mm
Tube diameter
14 mm
Inner diameter
10 mm
Number of tubes
3
Approximate weight
9.8 kg/m
Number of cores
3
Electrical characteristics
Electrical characteristics
Perm. current rating buried 15°C - trefoil formation
735 A
Perm. current rating in air 25°C - trefoil formation
945 A
Max. DC resistance of the conductor at 20°C
0.0469 Ohm/km
Permissible short circuit current conductor 1s
59.5 kA
Nominal phase capacitance
0.43 µF / km
Inductive reactance at 50Hz
- Ohm/km
Nominal inductance
- mH/km
Phase reactance 50 Hz - trefoil formation
0.09 Ohm/km
Zero sequence reactance at 50HZ
- Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
56.7 kN
Minimum repeated bending diameter
1080 mm
Usage characteristics
Usage characteristics
Packaging
NX26
Length
350 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)