TSLF-OF 36kV 1x240A G24

Description

Description

Standards

  • Product
    HD 620.10K

User benefits:

Diffusion free high voltage cable. Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime.

The semiconducting layer makes it easy to test the outer sheats integrity while on drum, before backfilling, in plastic tubes etc.

Screen section: Value given is the physical cross section of the copper wires in one core.

 

A tube with an optical fibre inside is taped to the cable surface.

Usage:

Indoor

Underground

Outdoors

Intended for high voltage energy distribution

Fire properties:

Halogen free

Cable marking:

NEXANS NS TSLF XX kV 1 x mm²/mm² MONTH YEAR

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
MDPE
Halogen free
Yes
Fiber optic type
SingleMode 9/125

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Conductor diameter
18.2 mm
Diameter over insulation
35.5 mm
Nominal insulation thickness
8.0 mm
Earth conductor cross section
35 mm²
Screen section
21 mm²
Average sheath thickness
2.6 mm
Tube diameter
14 mm
Inner diameter
10 mm
Number of optical fibres
24
Height
58.2 mm
Nominal outer diameter
44.2 mm
Approximate weight
2.011 kg/m

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - flat formation
450 A
Perm. current rating buried 15°C - trefoil formation
450 A
Perm. current rating in air 25°C - flat formation
- A
Perm. current rating in air 25°C - trefoil formation
530 A
Nominal phase capacitance
0.21 µF / km
Permissible short circuit current conductor 1s
22.7 kA
Nominal inductance
- mH/km
Phase reactance 50 Hz - trefoil formation
0.12 Ohm/km
Zero sequence reactance at 50HZ
- Ohm/km
Max. DC resistance of the conductor at 20°C
0.0778 Ohm/km
Maximum operating voltage
36 kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
7.2 kN
Minimum repeated bending diameter
884 mm

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
10 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close