TSLF-OFJ 24kV 3x1x50A KGF25 G48

Description

Description

Standards

  • Product
    HD 620.10K

User benefits:

Diffusion free high voltage cable. Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime.

The semiconducting layer makes it easy to test the outer sheats integrity while on drum, before backfilling, in plastic tubes etc.

The cable has one tube witch includes an optical fiber cable, and one ground wire.

Usage:

Indoor

Underground

Outdoors

Intended for high voltage energy distribution

Fire properties:

Halogen free

Cable marking:

NEXANS NS TSLF-OFJ XX kV 1 x mm²/mm² MONTH YEAR

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
MDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Conductor diameter
8.0 mm
Diameter over insulation
19.3 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
16 mm²
Screen section
10 mm²
Average sheath thickness
2.1 mm
Nominal outer diameter
58.2 mm
Tube diameter
14 mm
Inner diameter
10 mm
Number of optical fibres
48
Ground conductor cross-section
25 mm²
Approximate weight
2.466 kg/m
Number of cores
3

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - trefoil formation
180 A
Perm. current rating in air 25°C - trefoil formation
190 A
Max. DC resistance of the conductor at 20°C
0.641 Ohm/km
Permissible short circuit current conductor 1s
4.7 kA
Nominal phase capacitance
0.16 µF / km
Inductive reactance at 50Hz
1 Ohm/km
Nominal inductance
1 mH/km
Phase reactance 50 Hz - trefoil formation
0.11 Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
4.5 kN
Minimum repeated bending diameter
582 mm

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close