- Products
- Segments
- Newsroom
- Tools and Resources
- Sustainability
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
TSLF-OJ 24kV three cores with tubes and copper wire
TSLF-OJ 24kV three cores with tubes and copper wire
Metal screened cable with laminated aluminium and outer semiconducting layer. Three cores twisted together with two tubes for future installation of optical cable and one ground conductor
Read moreTSLF-OJ 24kV 3x1x50A KGF50
Nexans ref. 10164094 - Country ref. 1021292
- Packaging: Drum (500m)
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 58.2 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 2.63 kg/m
- Maximum Pulling Tension: 4.5 kN
TSLF-OJ 24kV 3x1x50A KGF25
Nexans ref. 10174447 - Country ref. 1021241
- Packaging: Drum (500m)
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 58.2 mm
- Ground conductor cross-section: 25 mm²
- Approximate weight: 2.44 kg/m
- Maximum Pulling Tension: 4.5 kN
TSLF-OJ 24kV 3x1x95A KGF50
Nexans ref. 10164095 - Country ref. 1021294
- Packaging: Drum (500m)
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 65.9 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 3.44 kg/m
- Maximum Pulling Tension: 8.55 kN
TSLF-OJ 24kV 3x1x95A KGF25
Nexans ref. 10174448 - Country ref. 1021243
- Packaging: Drum (500m)
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 65.9 mm
- Ground conductor cross-section: 25 mm²
- Approximate weight: 3.25 kg/m
- Maximum Pulling Tension: 8.55 kN
TSLF-OJ 24kV 3x1x150A KGF50
Nexans ref. 10164096 - Country ref. 1021296
- Packaging: Drum (500m)
- Conductor cross-section: 150 mm²
- Nominal outer diameter: 72.6 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 4.15 kg/m
- Maximum Pulling Tension: 13.5 kN
TSLF-OJ 24kV 3x1x150A KGF25
Nexans ref. 10174449 - Country ref. 1021245
- Packaging: Drum (500m)
- Conductor cross-section: 150 mm²
- Nominal outer diameter: 72.6 mm
- Ground conductor cross-section: 25 mm²
- Approximate weight: 3.96 kg/m
- Maximum Pulling Tension: 13.5 kN
TSLF-OJ 24kV 3x1x240A KGF50
Nexans ref. 10164097 - Country ref. 1021298
- Packaging: Drum (500m)
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 82.1 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 5.51 kg/m
- Maximum Pulling Tension: 21.6 kN
TSLF-OJ 24kV 3x1x240A KGF25
Nexans ref. 10174451 - Country ref. 1021247
- Packaging: Drum (500m)
- Conductor cross-section: 240 mm²
- Nominal outer diameter: 82.1 mm
- Ground conductor cross-section: 25 mm²
- Approximate weight: 5.32 kg/m
- Maximum Pulling Tension: 21.6 kN
TSLF-OJ 24kV 3x1x400A KGF50 16 mm rør
Nexans ref. 10561300 - Country ref. 1087894
- Packaging: Drum (300m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 95.5 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 7.34 kg/m
- Maximum Pulling Tension: 36 kN
TSLF-OJ 24kV 3x1x400A KGF25
Nexans ref. 10558652 - Country ref. 1087888
- Packaging: Drum (300m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 95.5 mm
- Ground conductor cross-section: 25 mm²
- Approximate weight: 7.14 kg/m
- Maximum Pulling Tension: 36 kN
TSLF-OJ 24kV 3x1x400A KGF50
Nexans ref. 10557076 - Country ref. 1087875
- Packaging: Drum (300m)
- Conductor cross-section: 400 mm²
- Nominal outer diameter: 95.5 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 7.33 kg/m
- Maximum Pulling Tension: 36 kN
TSLF-OJ 24kV 3x1x630A KGF50
Nexans ref. 10576989 - Country ref. 1007656
- Packaging: Drum (300m)
- Conductor cross-section: 630 mm²
- Nominal outer diameter: 110.0 mm
- Ground conductor cross-section: 50 mm²
- Approximate weight: 10 kg/m
- Maximum Pulling Tension: 56.7 kN
Description
Description
Standards
-
ProductHD 620.10K
User benefits:
Diffusion free high voltage cable. Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime.
The semiconducting layer makes it easy to test the outer sheats integrity while on drum, before backfilling, in plastic tubes etc.
The cable has two tubes for future installation of optical cables and one ground conductor.
Usage:
Indoor
Underground
Outdoors
Intended for high voltage energy distribution
Fire properties:
Halogen free
Cable marking:
NEXANS NS TSLF 12 kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania