- Products
- Segments
- Newsroom
- Tools and Resources
- Sustainability
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
TSLI 24kV 1x240AQ
TSLI 24kV 1x240AQ
TSLI 24kV 1x240AQ
Read more- Nexans ref. : 10251789
- Country ref. : 1017527
- EAN : 7045210076219
Description
Description
Standards
-
ProductHD 620.10K
-
TestIEC 60332-3 Cat.C
User benefits:
Diffusion free high voltage cable
Avoids threfore growth of watertrees in the XLPE insulation which increases the lifetime.
Outer sheath of fire retardent material
Meter marks
Usage:
Indoor
Tunnels
Industrial installations
Surroundings which require a fire retardent cable
Fire properties:
Fire retardent
Halogenfree
Cable marking:
NEXANS NS TSLI XX kV 1 x mm²/mm² MONTH YEAR, metermarks
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Outer sheath
Flame retardant polymer compound
Radial waterproof
Yes
Conductor flexibility
Class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
240 mm²
Conductor diameter
18.2 mm
Nominal insulation thickness
5.5 mm
Diameter over insulation
29.5 mm
Screen section
21 mm²
Average sheath thickness
2.2 mm
Nominal outer diameter
37.6 mm
Approximate weight
1683 kg/km
Number of cores
1
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.11 Ohm/km
Phase reactance 50 Hz - flat formation
0.17 Ohm/km
Maximum operating voltage
24 kV
Perm. current rating buried 15°C - flat formation
465 A
Perm. current rating buried 15°C - trefoil formation
455 A
Perm. current rating in air 25°C - flat formation
515 A
Perm. current rating in air 25°C - trefoil formation
490 A
Permissible short circuit current
21600 A
Nominal phase capacitance
0.28 µF / km
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Mechanical characteristics
Mechanical characteristics
Maximum pulling force by laying
7.2 kN
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Minimum installation temperature
-20 °C
Bending factor when laying
15 (xD)
Fire retardant
IEC 60332-3-24 (cat C)
Resources
Resources
Selling & delivery Information
Cable marking:
NEXANS NS TSLI XX kV 1 x mm²/mm² MONTH YEAR, metermarks
Lifemark
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania