TSLI 36kV 1x400A/35
Description
Description
Standards
-
ProductHD 620.10K
-
TestIEC 60332-3 Cat.C
User benefits
- Diffusion free high voltage cable
- Avoids threfore growth of watertrees in the XLPE insulation which increases the lifetime.
- Outer sheath of fire retardant material
- Meter marks
Application
- Indoor
- Tunnels
- Industrial installations
- Surroundings which require a fire retardent cable
Fire properties
- Fire retardent
- Halogenfree
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Outer sheath
Flame retardant polymer compound
Radial waterproof
Yes
Conductor flexibility
Class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
400 mm²
Conductor diameter
23.6 mm
Nominal insulation thickness
8.0 mm
Diameter over insulation
41.1 mm
Screen section
35 mm²
Average sheath thickness
2.8 mm
Nominal outer diameter
50.0 mm
Approximate weight
2850 kg/km
Number of cores
1
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.0778 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.11 Ohm/km
Phase reactance 50 Hz - flat formation
0.16 Ohm/km
Maximum operating voltage
36 kV
Perm. current rating buried 15°C - flat formation
565 A
Perm. current rating buried 15°C - trefoil formation
580 A
Perm. current rating in air 25°C - flat formation
745 A
Perm. current rating in air 25°C - trefoil formation
705 A
Permissible short circuit current
36000 A
Nominal phase capacitance
0.26 µF / km
Rated Voltage Uo/U (Um)
18 / 30 (36) kV
Mechanical characteristics
Mechanical characteristics
Maximum pulling force by laying
12 kN
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Minimum installation temperature
-20 °C
Bending factor when laying
15 (xD)
Fire retardant
IEC 60332-3-24 (cat C)
Resources
Resources
Selling & delivery Information
Cable marking:
NEXANS NS TSLI XX kV 1 x mm²/mm² MONTH YEAR, metermarks
Lifemark