TSLI 24kV 3x1x240A

Description

Description

Standards

  • Product
    HD 620.10K; IEC 60228; IEC 60502-2
  • Test
    IEC 60332-3 Cat.C

User benefits:

Diffusion free high voltage cable.

Avoids therefore growth of water trees in the XLPE insulation which increases the lifetime

Usage:

Indoor

Tunnels

Industrial installations

Outdoors

Intended for high voltage energy distribution

Fire propertirs:

Fire retardent

Halogen free

Cable marking:

NEXANS NS TSLI XX kV 1 x mm²/mm² MONTH YEAR

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Individual sheath
Outer sheath
Fire-retardant
Halogen free
Yes
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Average insulation thickness
5.5 mm
Conductor cross-section
240 mm²
Conductor diameter
18.2 mm
Diameter over insulation
29.5 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
35 mm²
Screen section
21 mm²
Average sheath thickness
2.5 mm
Nominal outer diameter
82.1 mm
Approximate weight
4.95 kg/m
Approximate weight
5075 kg/km
Number of cores
3

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - trefoil formation
445 A
Perm. current rating in air 25°C - trefoil formation
525 A
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Permissible short circuit current conductor 1s
21.6 kA
Nominal phase capacitance
0.28 µF / km
Phase reactance 50 Hz - trefoil formation
0.11 Ohm/km
Permissible short circuit current
21600 A
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
21.6 kN
Minimum repeated bending diameter
821 mm

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000997-NOLA
  • Certification Date : 3/10/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 0081
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close