- Products
- Segments
- Newsroom
- Tools and Resources
- Sustainability
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
TSLI 24kV 3x1x150A MP
TSLI 24kV 3x1x150A MP
Metal screened cable with laminated aluminium and polyethylene sheath. Three twisted cores with a red searchable marking stripe.
Read more- Nexans ref. : 10569681
- Country ref. : 1087814
- EAN : 7045210132335
Description
Description
User benefits:
Diffusion free high voltage cable
Avoids therefore growth of watertrees in the XLPE insulation which increases the lifetime.
Usage:
Indoor
Tunnels
Industrial installations
Outdoor
Surroundings which require a fire retardent cable
Fire properties:
Fire retardent
Halogenfree
Cable marking:
NEXANS NS TSLI XX kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
Fire-retardant
Halogen free
Yes
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Approximate weight
3.61 kg/m
Average insulation thickness
5.5 mm
Average sheath thickness
2.3 mm
Conductor cross-section
150 mm²
Conductor diameter
14.1 mm
Diameter over insulation
25.4 mm
Earth conductor cross section
25 mm²
Nominal insulation thickness
5.5 mm
Nominal outer diameter
72.6 mm
Number of cores
3
Screen section
15 mm²
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Maximum operating voltage
24 kV
Nominal phase capacitance
0.23 µF / km
Perm. current rating buried 15°C - trefoil formation
340 A
Perm. current rating in air 25°C - trefoil formation
385 A
Permissible short circuit current
13500 A
Permissible short circuit current conductor 1s
13.5 kA
Phase reactance 50 Hz - trefoil formation
0.12 Ohm/km
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
13.5 kN
Minimum repeated bending diameter
726 mm
Usage characteristics
Usage characteristics
Bending factor when laying
5 (xD)
Maximum operating temperature
90 °C
Minimum installation temperature
-20 °C
Short-circuit max. conductor temperature
250 °C
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania