TXSI 24kV 1x25 mm² CU

Description

Description

Standards

  • Product
    HD 620.10K; IEC 60228
  • Test
    IEC 60332-3 Cat.C

User benefits:

Outer sheath of fire retardent material

Meter marks

Usage:

Indoor

Outdoor

Tunnels

Industrial installations

Surroundings which require a fire retardent cable

Fire properties:

Fire retardent

Cable marking:

NEXANS NS TXSI 24 kV 1 x 25 mm² MONTH YEAR, metermarks

Lifemark

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper class 2
Conductor shape
Circular compacted
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wires / 6mm²
Outer sheath
Halogen free compound
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
25 mm²
Conductor diameter
6.0 mm
Diameter over insulation
18.3 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
16 mm²
Screen section
16 mm²
Average sheath thickness
1.7 mm
Nominal outer diameter
25.1 mm
Approximate weight
0.8 kg/m
Number of cores
1

Electrical characteristics

Electrical characteristics

Perm. current rating buried 15°C - flat formation
185 A
Perm. current rating buried 15°C - trefoil formation
170 A
Perm. current rating in air 25°C - flat formation
175 A
Perm. current rating in air 25°C - trefoil formation
160 A
Max. DC resistance of the conductor at 20°C
0.727 Ohm/km
Permissible short circuit current conductor 1s
3.5 kA
Nominal phase capacitance
0.14 µF / km
Phase reactance 50 Hz - flat formation
0.23 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.15 Ohm/km
Resistance of the screen
1.15 Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV

Mechanical characteristics

Mechanical characteristics

Minimum repeated bending diameter
502 mm
Maximum Pulling Tension
1.25 kN

Usage characteristics

Usage characteristics

Length
1000 m
Maximum operating temperature
90 °C
Minimum installation temperature
-20 °C
Fire retardant
IEC 60332-3-24 (cat C)
Bending factor when laying
10 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close