PFXP 0.6/1kV 5G10

Description

Description

Standards

  • Product
    HD 603.3J
  • Test
    EN 50265; IEC 60332-1

Industrial cable for use on cable ladders and in ducts and pipes. Also recommended for installation in insulated walls without any extra protection. The cable may also be used in non-explosive areas in mines and tunnels. Recommended used on walls outdoor where the cable is not exposed to mechanical stress.  The cable may be used on low voltage installations 230V, 400V and 690V.

The cable is double insulated and may therefor be installed directly into the ground for underground service. For this application, extra mechanical protection such as protection boards must be used.  

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Sheath colour
Light grey
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
With Green/Yellow core
-
With smaller neutral conductor
No
Material of filler / inner sheath
Bedding or tape
Insulation
PVC
Lead free
Yes
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Nominal outer diameter
21.0 mm
Number of cores
5
Conductor cross-section
10 mm²
Approximate weight
84.0 kg/100m
Conductor diameter
3.9 mm
Neutral conductor section (when smaller)
- mm²
Number of strands
7

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Length
500 m
Packaging
Drum
Max. conductor temperature in service
70 °C

Resources

Resources

Current capacity table PVC insulation multicore single phase

PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
10.0 43.0 33.0 52.0 41.0 63.0 49.0 60.0 47.0 64.0 0.0 70.0 54.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table PVC insulation multicore three phase

PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
10.0 39.0 31.0 46.0 36.0 57.0 44.0 50.0 39.0 54.0 0.0 60.0 46.0
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single-core or Multi-core cable in ducts in the ground
D2 Single-core or Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Selling & delivery Information

The cable is marked with LIFEMARK™.

Declaration of Performance

  • Declaration of Performance n� : 1000058-SEGR
  • Certification Date : 2/20/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close