FL-EXXE 1 kV 4G50A

Description

Description

Power distribution cable, designated for entry point installation or other general outdoor use (UV-resistant).

The cable is halogen free, TPI insulated and  PE sheathed. Each phase having insulation and an outer sheath.

The cable can be placed directly in soil.

The conductor is made of Low Carbon Aluminum, reducing the carbon footprint of the Cable compared to standard aluminum. 

Every part of the cable is reciclable due to the utilization of Thermoplastic insulation, TPI.

The outer sheath consist of at least 30% recycled PE.

 

When laying at a lower temperature than 0°C, care must be taken to avoid damage to the outer sheath. It is especially important that the cable is not exposed to impact at temperatures below 0 °C.

When laying at a lower temperature than -10 °C, the cable should be preheated before laying.

If the cable is cut and not installed immediately, each phase must be sealed, to prevent water intrusion.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Type of conductor
Circular compacted stranded
Insulation
Thermoplastic material
With Green/Yellow core
Yes
Halogen free
Yes
Outer sheath
Partly recycled polyethylene
Conductor flexibility
Stranded class 2
Conductor shape
Round, stranded

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Conductor diameter
8.0 mm
Number of cores
4
Diameter over insulation
10.0 mm
Nominal outer diameter
31.0 mm
Approximate weight
0.9 kg/m

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
170 A
Permissible current rating when buried
190 A
Max. DC resistance of the conductor at 20°C
0.641 Ohm/km
Inductive reactance at 50Hz - trefoil
0.095 Ohm/km
Nominal inductance
0.3 mH/km
Zero sequence reactance at 50HZ
0.38 Ohm/km
Zero sequence resistance at 20°C
2.56 Ohm/km
Capacity of phase cores approx.
0.08 µF / km
Permissible short circuit current conductor 1s
4.5 kA
Maximum operating voltage
1000 V
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
6 kN
Minimum repeated bending diameter
186 mm

Usage characteristics

Usage characteristics

Packaging
NX12
Length
700 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-15 °C
Bending factor when laying
6 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close