TFXP-O 1kV 4G95mm²A

Description

Description

Standards

  • Product
    HD 603.5M
  • Test
    IEC 60332-1

User benefits:

The cable is specially devoloped for low temperature conditions. It is used as a distribution cable for houses, and has an outer tube for future installation of optical cable. Fibre optic microcables as B-Lite Green could be used in any power cable with fibre tube or in standard cableway of microducts.

Installation:

  • Underground 
  • Outdoor


Usage

  • Energy distribution


Marking

NEXANS GS TFXP-O n x mm2 1kV YEAR MONTH

Conductor marking/colour code

Black-Brown-Grey-Green/Yellow

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Sector-shaped stranded (SM)
Insulation
XLPE (chemical)
With Green/Yellow core
Yes
Material of filler / inner sheath
PE
Outer sheath
PVC
Sheath colour
Green
Conductor flexibility
Stranded class 2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
95 mm²
Conductor diameter
- mm
Sector-shaped heigth
12.4 mm
Sector-shaped width
17.4 mm
Number of cores
4
Nominal outer diameter
38.0 mm
Tube diameter
12 mm
Inner diameter
9 mm
Height
55 mm
Approximate weight
1.74 kg/m

Electrical characteristics

Electrical characteristics

Permissible current rating in open air
245 A
Permissible current rating when buried
260 A
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Inductive reactance at 50Hz
0.075 Ohm/km
Nominal inductance
0.23 mH/km
Zero sequence reactance at 50HZ
0.31 Ohm/km
Zero sequence resistance at 20°C
1.28 Ohm/km
Capacity of phase cores approx.
0.12 µF / km
Permissible short circuit current conductor 1s
8.6 kA
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
11.4 kN
Minimum repeated bending diameter
456 mm

Usage characteristics

Usage characteristics

Packaging
NX16
Length
500 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-10 °C
Bending factor when laying
6 (xD)
Flame retardant
IEC 60332-1
U.V resistance
Yes

Resources

Resources

Documentation

PEP pdf — 4.3 MB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close