- Products
- Segments
- Newsroom
- Tools and Resources
- Sustainability
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
TSLF(HD) 24kV 3x1x95A MP
TSLF(HD) 24kV 3x1x95A MP
Metal screened cable with laminated aluminium sheet and outer semiconducting layer. Three twisted cores and a red marking stripe.
Read more- Nexans ref. : 10567117
Description
Description
Standards
-
ProductHD 620.10K
User benefits:
Diffusion free high voltage cable.
Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.
Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.
Screen section: Value given is the physical cross section of the copper wires in the screen of one core.
Usage:
Indoor
Underground
Outdoors
Intended for high voltage energy distribution
Fire propertirs:
Halogen free
Cable marking:
NEXANS NS TSLF 12 kV 1 x mm²/mm² MONTH YEAR
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
XLPE (chemical)
Material of the external semi-conductor
Extruded
Screen
Copper wire
Armour type
Aluminium foil
Radial waterproof
Yes
Outer sheath
HDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
95 mm²
Conductor diameter
11.4 mm
Diameter over insulation
22.7 mm
Nominal insulation thickness
5.5 mm
Earth conductor cross section
25 mm²
Screen section
15 mm²
Average sheath thickness
2.2 mm
Nominal outer diameter
65.9 mm
Approximate weight
2.87 kg/m
Number of cores
3
Electrical characteristics
Electrical characteristics
Perm. current rating buried 15°C - trefoil formation
265 A
Perm. current rating in air 25°C - trefoil formation
295 A
A.C. Conductor resist. 50Hz and at 90 °C
- Ohm/km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Permissible short circuit current conductor 1s
9 kA
Nominal phase capacitance
0.2 µF / km
Inductive reactance at 50Hz - trefoil
- Ohm/km
Phase reactance 50 Hz - trefoil formation
0.12 Ohm/km
Maximum operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
8.55 kN
Minimum repeated bending diameter
659 mm
Usage characteristics
Usage characteristics
Packaging
NX22
Length
500 m
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when laying
5 (xD)
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania