- Products
- Segments
- Newsroom
- Tools and Resources
- Sustainability
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
TSLF 72 kV 1x240A 14 mm insulation
TSLF 72 kV 1x240A 14 mm insulation
Metal screened cable with aluminium sheath and outer semiconducting layer
Read more- Nexans ref. : 10239174
- EAN : 7611755581589
Description
Description
Standards
-
TestIEC 60840
User benefits:
Diffusion free high voltage cable
Avoids growth of watertrees in the XLPE insulation and increases the lifetime of the cable.
Sheath integrity may be tested while on drum, before backfilling, in plastic pipes etc.
Meter marks
Screen section: Value given is the physical cross section of the copper wires in the screen.
Usage: Indoor, Underground, Outdoors
Intended for high voltage energy distribution
Fire properties:
Halogenfree
Cable marking:
NEXANS NS TSLF kV 1 x mm²/mm² MONTH YEAR, metermarks
Lifemark
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular compacted
Material used for longitudinal water tightness
Swelling powder
Material of the inner semi-conductor
Extruded
Insulation
Extruded XLPE compound
Material of the external semi-conductor
Extruded
Screen
Copper wire
Radial waterproof
Yes
Outer sheath
MDPE
Outer conductive layer
Yes
Halogen free
Yes
Conductor flexibility
Stranded class 2
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
240 mm²
Conductor diameter
18.2 mm
Nominal insulation thickness
14.0 mm
Diameter over insulation
48.5 mm
Earth conductor cross section
- mm²
Screen section
21 mm²
Average sheath thickness
3.0 mm
Nominal outer diameter
60.0 mm
Approximate weight
3.17 kg/m
Number of cores
1
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Phase reactance 50 Hz - trefoil formation
0.13 Ohm/km
Phase reactance 50 Hz - flat formation
0.2 Ohm/km
Maximum operating voltage
72 kV
Perm. current rating buried 15°C - flat formation
450 A
Perm. current rating buried 15°C - trefoil formation
445 A
Perm. current rating in air 25°C - flat formation
575 A
Perm. current rating in air 25°C - trefoil formation
530 A
Permissible short circuit current conductor 1s
21.6 kA
A.C. Conductor resist. 50Hz and at 90 °C
- Ohm/km
Nominal phase capacitance
0.16 µF / km
Rated Voltage Uo/U (Um)
36/66 (72,5) kV
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
7.2 kN
Minimum repeated bending diameter
1200 mm
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Minimum installation temperature
-20 °C
Bending factor when installed
- (xD)
Bending factor when laying
10 (xD)
Length
- m
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania